Calculator

Wire Size & Voltage Drop Calculator

Find the right AWG wire gauge and check voltage drop for a copper or aluminum run — using NEC 310.16 ampacity and the standard circular-mils method.

How it works

Voltage drop is calculated with the circular-mils method used throughout the trade:

Vdrop = (K × I × L × P) ÷ CM

Drop % = Vdrop ÷ system voltage × 100. The recommended wire is the smallest gauge that is both rated for the current (NEC 310.16, 75 °C column) and stays under your voltage-drop target.

AWG reference (copper, 75 °C)

AWGCircular milsAmpacity (A)

Ampacity values are the 75 °C column of NEC Table 310.16 for copper. Aluminum carries less current for the same size; this tool applies the aluminum resistivity for voltage drop but you should confirm aluminum ampacity separately.

Common questions

Why does voltage drop matter?

Excess drop means motors run hot, lights dim, and heaters underperform — and it wastes energy as heat in the wire. The NEC recommends (does not mandate) ≤3% on a branch circuit and ≤5% total from service to outlet.

Do I use one-way or round-trip distance?

Enter the one-way distance. The path factor (2 for single-phase) already accounts for current flowing out and back.

Copper or aluminum?

Aluminum is cheaper and lighter but needs a larger gauge for the same load and requires listed connectors and anti-oxidant. Copper is the default for branch circuits.

Educational tool — not a substitute for a licensed electrician. Results use standard formulas and NEC 310.16 values but do not account for ambient temperature, conductor bundling/derating, termination ratings, breaker rules, or local code. Always verify against the current NEC and have work reviewed by a qualified professional.